IMI Norgren 0882200 18D G1/4 Hydraulic Pressure Switch, 10 to 160 bar

Norgren 0882200 is a threaded G1/4 hydraulic switch for a 10 to 160 bar setpoint band.

Request a Quote

SKU: 0882200 Category: Tags: , Brand:

Description

This mid-range DIN version uses a fixed switching difference. Plan for the recovery point before specifying a circuit that cycles near the pressure trip.

Request a Quote

0882200 Configuration

Model 0882200
Marked model 0882200
Pressure connection G1/4
Setpoint range 10 to 160 bar
Differential Fixed
Marked Pmax 400 bar

Selection Notes for 0882200

Compare required trip and recovery with the range-end values. They are not a formula for the differential at an intermediate setpoint.

Threaded Model Switching Difference

Published band Lower-range difference Upper-range difference
10 to 160 bar 11 bar 17 bar

Threaded Body Fit: Drawing 1

Selection criterion Catalogue information
Body width 30 mm
Main body length dimension 72 mm
Port-end extension shown 7.5 mm
Port wrench flats 27 mm

Setpoint Placement

The applicable table uses atmospheric pressure as reference and recommends a setpoint near the middle of the band where practicable. The 400 bar nameplate maximum does not extend the adjustment span.

Leave Room for the DIN Connector

Compare the threaded body envelope and confirm room for the electrical plug. The drawing also illustrates an M12 option, but the selected G1/4 code is in the DIN table.

Installation Preparation

Prepare the equipment according to the site procedure and the manufacturer's instructions before installing this part. Where relevant, isolate power and pressure sources, then check the mounting direction, connection points, and sealing arrangement. After installation, inspect the completed connections before beginning a controlled functional test.

Order Detail Confirmation

To help prepare an accurate spare-parts order, please include the full model code, required quantity, and delivery destination in your enquiry. Photos or existing purchase records may be useful when a suffix or replacement choice is uncertain. Product details, payment method, and shipping arrangement can then be reviewed together before order processing.

Additional information

Model

0882200

Marked model

0882200

Pressure connection

G1/4

Setpoint range

10 to 160 bar

Differential

Fixed

Marked Pmax

400 bar