Norgren 1801115 20D G1/2 Mechanical Pressure Switch

1801115: Electromechanical pressure switch with a 0.05-1 bar setting range, G1/2 process connection and adjustable hysteresis.

Request a Quote

SKU: 1801115 Category: Tags: , Brand:

Description

The 1801115 uses a gold plated microswitch and stainless steel bellows to provide pressure dependent switching in neutral or aggressive, nonflammable gases and fluids. The cable gland version has an IP66 enclosure for industrial installations.

Request a Quote

Selection Notes for 1801115

Select a setpoint near the middle of the 0.05-1 bar range. Check the required switching differential, fluid compatibility and electrical load before connecting the switch; pressure pulsations are not permitted.

Pressure switching configuration

Parameter Value
Setting range 0.05-1 bar
Switching differential Adjustable
Minimum differential at lower range 0.08 bar
Minimum differential at upper range 0.11 bar
Maximum differential 0.7 bar
Process connection G1/2
Electrical entry M20 x 1.5 cable gland
Weight 1.1 kg

Service conditions and construction

Parameter Value
Medium Neutral or aggressive nonflammable gases and fluids
Maximum viscosity 1000 mm2/s
Ambient temperature -25 to +80 C
Media temperature -10 to +100 C
Repeatability +/-1% of final value, depending on regulating pressure
Housing Die cast aluminium
Sensor and sealing Stainless steel sensor and bellows
Protection IP66 with cable gland
Pulsations Not permitted

Gold contact switching capacity

Parameter Value
Maximum switching frequency 20 cycles/min
Mechanical life 10000000 switching cycles
AC inductive load, 250 V, cos phi 0.7 3 A
DC resistive load, 250 V 0.4 A
DC inductive load, 125 V, L/R 10 ms 0.05 A
Reference temperature +20 C

Setpoint and differential

For stable operation, position the setpoint near the middle of the 0.05-1 bar setting range. Minimum adjustable switching differential is 0.08 bar at the lower range and 0.11 bar at the upper range; maximum adjustable differential is 0.7 bar. The overpressure limit is a maximum testing value and must not be used as an operating setpoint.

Fluid and mounting requirements

The stainless steel sensor and bellows are suitable for compatible neutral or aggressive nonflammable gases and fluids up to 1000 mm2/s. Mounting position is unrestricted. Avoid shock and vibration where possible, and do not apply pressure pulsations.

Electrical load selection

Gold plated contacts support low level switching as well as industrial control loads, but allowable current depends on voltage and load type. At 250 V DC, the resistive limit is 0.4 A. At 125 V DC, the inductive limit is 0.05 A for L/R = 10 ms. Use appropriate arc suppression for inductive loads and observe correct polarity for a suppression diode.

Product Inquiry Support

We assist customers with industrial automation spare-part enquiries, including model confirmation, replacement questions, and initial photo comparisons. If you are unsure which version is installed, you may send the complete model code and clear photos of the nameplate or component. We will use the information provided to help review the enquiry and identify details that still need confirmation.

Additional information

Model

1801115

Pressure range

0.05-1 bar

Process connection

G1/2

Hysteresis

Adjustable

Electrical entry

M20 x 1.5 cable gland